What height does a pull station need to be?

What height does a pull station need to be?

Manual Fire Alarm Boxes (Pull Stations) – The height of the manual fire alarm boxes shall be a minimum of 42 inches and a maximum of 54 inches measured vertically, from the floor level to the activating handle or lever of the box. Manual fire alarm boxes shall be red in color.

What are the code requirements for manual pull stations?

NFPA 72 requires that manual pull stations be installed within 60 inches of the exit doorway of each exit, mounted between 42 inches and 48 inches to the center of the handle, and, among other things, be red in color.

Where must a fire alarm pull station be located?

NFPA 72 requires a pull station within 60 inches of every individual exit, and for groups of doors that are more than 40 feet wide away from each other, there must be a pull station on both sides of the grouping. The placement of fire alarm pull stations is critical to ensuring they provide the protection intended.

What is the NFPA code for fire alarm systems?

NFPA 72 only provides requirements for the installation, performance, testing, inspection, and maintenance of the fire alarm system. NFPA 101®, Life Safety Code® and other codes determine whether a fire alarm system is required in a given occupancy. 2.

Do fire alarm pull stations have to be red?

The location of your fire alarm pull stations will depend on the design and occupancy of your building. Additionally, a fire alarm pull station needs to be red and in a location that is completely unobstructed from obstacles. This way, anyone can access the pull station in an emergency.

Are fire alarms required by OSHA?

OSHA’s employee alarm systems standard 29 CFR 1910.165 applies to all employers that use an alarm system to satisfy any OSHA standard that requires employers to provide an early warning for emergency action, or reaction time for employees to safely escape the work place, the immediate work area, or both.

What is standard of fire alarm system?

ISO 7240-14:2013 specifies the design, installation, commissioning, and service requirements for a fire detection and alarm system (FDAS), which is primarily intended to provide early detection of fire and notification within one or more specified indoor or outdoor areas for the protection of lives.

Is NFPA 1221 mandatory?

Reflecting industry changes and new technologies, the 2016 edition of NFPA 1221 is essential to public welfare in every community. NFPA 1221 provides procedural and physical criteria for the installation, performance, operation, and maintenance of public emergency services communications systems and facilities.

How do fire alarm pull stations work?

Pull stations send a signal to the control panel, and if the fire alarm is monitored, the control panel then usually sends a message to a company’s monitoring service, which transmits that message to first responders. In some cases, a signal is transmitted directly to a fire department.

When should a fire alarm be pulled?

If you smell or see smoke or fire, alert others in the nearby area, activate the fire alarm by pulling a fire alarm pull station and evacuate. WHEN A FIRE ALARM IS ACTIVATED EVACUATION IS MANDATORY!

What OSHA standard describes the requirements for fires and employee alarm systems?

1910.165 – Employee alarm systems.

What is the maximum distance between smoke detectors?

The maximum distance between two smoke alarms should be 30 feet. If a hallway is greater than 30 feet, a smoke alarm must be installed at each end.

How many pull stations do I need for my fire alarm system?

NFPA 101 requires at least one manual pull station for any fire alarm system that uses automatic fire detection devices such as smoke detectors and heat sensors or water flow detection devices such as sprinklers. How many of them are required depends on how large the area to be protected is and how many exits it has.

What is the OSHA standard for alarm systems?

OSHA’s employee alarm systems standard 29 CFR 1910.165 applies to all employers that use an alarm system to satisfy any OSHA standard that requires employers to provide an early warning for emergency action, or reaction time for employees to safely escape the work place, the immediate work area, or both.

What is nfnfpa 72 fire alarm pull station?

NFPA 72 refers to fire alarm pull stations as “manual fire alarm boxes.” The code requires that the travel distance to the nearest pull station on a given floor must be no more than 200 feet. So, the larger the building and the longer its hallways, the more pull stations will be required.

What are the requirements for fire detection systems in the workplace?

29 CFR 1910.164, Fire detection systems What are the general requirements? 1910.165(b)(1) The employee alarm system shall provide warning for necessary emergency action as called for in the emergency action plan, or for reaction time for safe escape of employees from the workplace or the immediate work area, or both.